Cables in accordance with IEC 60502-1 are intended for fixed installation :

• indoors
• outdoors
• underground
• in water

(Note: The relevant national installation regulations must be observed) Nominal and highest cable voltages

 

Nominal rated voltage U0/U

Highest system voltage U0

kV

Three phase system (kV)

Single phase system (kV)

Single phase system (kV)

Low voltage (LV) acc to IEC 60502-1

0.6 / 1

1.2

1.4

0.7

1.8 / 3

3.6

4.2

2.1

Medium voltage (MV) acc to IEC 60502-2

3.6 / 6

7.2

8.3

4.2

6 / 10

12.0

14.0

7.0

8.7 / 15

17.5

20.0

10.0

12 / 20

24.0

28.0

14.0

18 / 30

36.0

42.0

21.0

 

1) both phases insulated
2) one phase grounded
3) max.voltage in d.c. systems 1.8 kv

U : Rated power-frequency voltage between phase conductors for which the cable is suitable.

U0 : Rated power-frequency voltage between conductor and earth or armour, metal sheath or screen for which the cable is suitabel.

Um : Maximum value of the “highest system voltage” between phase conductors for which the cable is suitable.

 

IEC Ratings

BSI Equivalent

U0 /U (Um) kV

1.8 / 3 (3.6) *

1.9 / 3.3 (3.6) *

3.3 / 6 (7.2)

3.8 / 6.6 (7.2)

6 / 10 (12)

6.35 / 11 (12)

8.7 / 15 (17.5)

8.7 / 15 (17.5)

12 / 20 (24)

12.7 / 22 (24)

18 / 30 (36)

19 / 33 (36)

 

* 1.8 kV cable is referred to IEC 60502-1 and BSI 5467